ANALISIS TINJAUAN DARI TOTAL HARMONIC DISTARTION ARUS MAUPUN TEGANGAN TERHADAP BEBAN SISI PRIMER DAN SISI SEKUNDER PADA TRANSFORMATOR
Abstract
Abstract: Andi Muhammad Ridwan Fikri and Muhammad Riswan T (2025) Analysis of Total Harmonic Distortion Current and Voltage Review of Primary and Secondary Side Loads on Transformers supervised by DR. Ir Zahir Zainuddin, M.T,. Rizal A Duyo, S.T,. M.T. The purpose of this study is to determine the comparison of linear and non-linear loads to harmonics on single-phase transformers. To determine the active power loss caused by single-phase transformers due to the influence of harmonics. The method used in this study is to conduct research and data collection at Jl. Sultan Alauddin No.259, Gn. Sari, Kec. Rappocini, Makassar City. The results obtained in this study are. With almost the same power, linear and non-linear loads have quite significant differences in terms of Total Harmonic Distortion (THD). THD current and voltage on non-linear loads are relatively greater than on linear loads. On the primary side of the THDi transformer, the linear load is 5.99% while the non-linear load is 68.25%, the THDV of the linear load is 1.51%, while the non-linear load is 1.60%. On the secondary side of the THDi transformer, the linear load is 1.18% while the non-linear load is 72.53%, the THDV of the linear load is 1.81%, while the non-linear load is 11.27%. This is because the non-linear load contains harmonics. The active power loss of the transformer due to harmonics generated by the non-linear load in this study was 0.024 kW, exceeding the standard set by the IEEE 519 standard, which is more than 10% of the total transformer rating of 0.022 kW. This can cause the transformer to overheat. While at a linear load of 0.019 kW, it can be said to be safe.
Abstract:Current,Voltage and Transformer
Full Text:
PDFReferences
F. Suryatmo, 2023, Teknik Listrik Instalasi Penerangan Jakarta, Renika Cipta.
Hamzah Berahim, Ir. Pengantar Teknik Tenaga Listrik. Andi Offset Yogyakarta, 2023.
Iskandar, ST. Sistem Pembangkit pada Sarana Bantu Navigasi Pelayaran, 2022.
Instalasi Listrik Arus Kuat n, Bina Cipta Bandung, 2022
Moh. Taib Sutan Sa'ti. Fisika. CV. Mandar Maju. Peraturan Umum Instalasi Listrik, LIPI, Jakarta 2022.
M. G - Say., 2022., Electrical Engineering Reference Handbook, 13 Thed, London, Bufferworth.
Marjunikadang, Jon. 2022. Studi efek harmonisa akibat penggunaan lampu hemat energi (LHE) di rumah tinggal atau rumah toko (ruko). Other thesis, Petra Christian University.
Peraturan Umum Instalasi Listrik Indonesia 2020 (PUID, Panitia Revisi PUIL Lembaga Ilmu Pengetahuan Indonesia, Jakarta.
Philips, 2022,, Compact Lighting Catalogue, Jakarta.
P. Van Harten & E. Setiawan Ir, 2022., Instalasi Listrik Arus Kuat I, Bandung, Bina Cipta.
Roger C. Dugan. Mark F. McGranaghan, Surya Santoso, H. Wayne Beaty. 2022. Electrical Power System Quality, Second Edition. New York : McGraw- Hill.
Terrell Croft; Clifford C. Corr; John Watt, 2021, American Electricians Hand Book,
Terrell Croft; Clifford C. Corr; John Watt, 2021, American Electricians Hand Book,
Zuhal, 1995. Dasar Teknik Tenaga Listrik dan Elektronika Daya. Jakarta : PT. Gramedia Pustaka Utama
Syafrudin, Dahaman. 2021. Effect of harmonic current componen to active power losses on power transformer.Proceeding 10th International Conference on Quality in Research (QIR). Depok : Engineering Center University of Indonesia
DOI: https://doi.org/10.26618/jte.v17i1.17087